RCT Senry 6FM100A-X 12V 100Ah Deep Cycle AGM Batteries (RCT BAT FM100A-X)

The rechargeable batteries are lead-lead dioxide systems.
The dilute sulfuric acid electrolyte is absorbed by separators and plates and thus immobilized.

Variant price modifier:
Base price with tax
WasR2528.99
Discount
Tax amount

Price includes VAT

RCT-Senry-6FM100A-X-12V-100Ah-Deep-Cycle-AGM-Batteries-(RCT-BAT--FM100A-X)-1.jpg_1
RCT Senry 6FM100A-X 12V 100Ah Deep Cycle AGM Batteries (RCT BAT  FM100A-X) RCT Senry 6FM100A-X 12V 100Ah Deep Cycle AGM Batteries (RCT BAT  FM100A-X)
Click on picture for a larger view.
+Delivery
Just R253 per month on Get this product with monthly repayments from MobiCred
Estimated Dispatch Time:
Click here to find out More
3-10d.gif

Would like to ask a question, please login.

Recommend this product to a friend

Description

RCT Senry 6FM100A-X 12V 100Ah Deep Cycle AGM Batteries (RCT BAT  FM100A-X)

Features and Specifications

Should the battery be accidentally overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is, therefore, maintenance-free, leak proof and usable in any position.

- Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance or water adding.
- Not restricted for air transport-complies with IATA/ICAO Special Provision A67.
- UL-recognized component.
- Can be mounted in any orientation.
- Computer designed lead, calcium tin alloy grid for high power density.
- Long service life, float or cyclic applications.
- Maintenance-free operation.
- Low self discharge.
- Case and cover available in both standard and flame retardant ABS.

Nominal Voltage     12V
Number of cells     6
Design Life     10 years
Nominal Capacity 25oC     
10 hour rate (10.0A, 10.8V)     100Ah
5 hour rate (17.5A, 10.5V)     79.8Ah
1 hour rate (66.2A, 9.6V)     65.2Ah
Internal Resistance     
Fully Charged battery 25oC     ≤5.7mOhms
Self-Discharge     
3% of capacity declined per month at 20oC(average)     
Operating Temperature Range     
Discharge     -20~60oC
Charge     -10~60oC
Storage     -20~60oC
Max. Discharge Current 25oC     900A(5s)
Short Circuit Current     2100A
Charge Methods: Constant Voltage Charge 25oC     
Cycle use     2.40-2.45VPC
Maximum charging current     30A
Temperature compensation     -30mV/oC
Standby use     2.20-2.30VPC
Temperature compensation     -20mV/oC